Previous  Home  Next



[Code of Federal Regulations]
[Title 29, Volume 8]
[Revised as of July 1, 2007]
From the U.S. Government Printing Office via GPO Access
[CITE: 29CFR1926.404]

[Page 247-254]
 
                             TITLE 29--LABOR
 
CHAPTER XVII--OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT 
                                OF LABOR
 
PART 1926_SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION--Table of Contents
 
                          Subpart K_Electrical
 
Sec. 1926.404  Wiring design and protection.

    (a) Use and identification of grounded and grounding conductors--(1) 
Identification of conductors. A conductor used as a grounded conductor 
shall be identifiable and distinguishable from all other conductors. A 
conductor used as an equipment grounding conductor shall be identifiable 
and distinguishable from all other conductors.
    (2) Polarity of connections. No grounded conductor shall be attached 
to any terminal or lead so as to reverse designated polarity.

[[Page 248]]

    (3) Use of grounding terminals and devices. A grounding terminal or 
grounding-type device on a receptacle, cord connector, or attachment 
plug shall not be used for purposes other than grounding.
    (b) Branch circuits--(1) Ground-fault protection--(i) General. The 
employer shall use either ground fault circuit interrupters as specified 
in paragraph (b)(1)(ii) of this section or an assured equipment 
grounding conductor program as specified in paragraph (b)(1)(iii) of 
this section to protect employees on construction sites. These 
requirements are in addition to any other requirements for equipment 
grounding conductors.
    (ii) Ground-fault circuit interrupters. All 120-volt, single-phase, 
15- and 20-ampere receptacle outlets on construction sites, which are 
not a part of the permanent wiring of the building or structure and 
which are in use by employees, shall have approved ground-fault circuit 
interrupters for personnel protection. Receptacles on a two-wire, 
single-phase portable or vehicle-mounted generator rated not more than 
5kW, where the circuit conductors of the generator are insulated from 
the generator frame and all other grounded surfaces, need not be 
protected with ground-fault circuit interrupters.
    (iii) Assured equipment grounding conductor program. The employer 
shall establish and implement an assured equipment grounding conductor 
program on construction sites covering all cord sets, receptacles which 
are not a part of the building or structure, and equipment connected by 
cord and plug which are available for use or used by employees. This 
program shall comply with the following minimum requirements:
    (A) A written description of the program, including the specific 
procedures adopted by the employer, shall be available at the jobsite 
for inspection and copying by the Assistant Secretary and any affected 
employee.
    (B) The employer shall designate one or more competent persons (as 
defined in Sec. 1926.32(f)) to implement the program.
    (C) Each cord set, attachment cap, plug and receptacle of cord sets, 
and any equipment connected by cord and plug, except cord sets and 
receptacles which are fixed and not exposed to damage, shall be visually 
inspected before each day's use for external defects, such as deformed 
or missing pins or insulation damage, and for indications of possible 
internal damage. Equipment found damaged or defective shall not be used 
until repaired.
    (D) The following tests shall be performed on all cord sets, 
receptacles which are not a part of the permanent wiring of the building 
or structure, and cord- and plug-connected equipment required to be 
grounded:
    (1) All equipment grounding conductors shall be tested for 
continuity and shall be electrically continuous.
    (2) Each receptacle and attachment cap or plug shall be tested for 
correct attachment of the equipment grounding conductor. The equipment 
grounding conductor shall be connected to its proper terminal.
    (E) All required tests shall be performed:
    (1) Before first use;
    (2) Before equipment is returned to service following any repairs;
    (3) Before equipment is used after any incident which can be 
reasonably suspected to have caused damage (for example, when a cord set 
is run over); and
    (4) At intervals not to exceed 3 months, except that cord sets and 
receptacles which are fixed and not exposed to damage shall be tested at 
intervals not exceeding 6 months.
    (F) The employer shall not make available or permit the use by 
employees of any equipment which has not met the requirements of this 
paragraph (b)(1)(iii) of this section.
    (G) Tests performed as required in this paragraph shall be recorded. 
This test record shall identify each receptacle, cord set, and cord- and 
plug-connected equipment that passed the test and shall indicate the 
last date it was tested or the interval for which it was tested. This 
record shall be kept by means of logs, color coding, or other effective 
means and shall be maintained until replaced by a more current record. 
The record shall be made available on the jobsite for inspection by the 
Assistant Secretary and any affected employee.

[[Page 249]]

    (2) Outlet devices. Outlet devices shall have an ampere rating not 
less than the load to be served and shall comply with the following:
    (i) Single receptacles. A single receptacle installed on an 
individual branch circuit shall have an ampere rating of not less than 
that of the branch circuit.
    (ii) Two or more receptacles. Where connected to a branch circuit 
supplying two or more receptacles or outlets, receptacle ratings shall 
conform to the values listed in Table K-4.
    (iii) Receptacles used for the connection of motors. The rating of 
an attachment plug or receptacle used for cord- and plug-connection of a 
motor to a branch circuit shall not exceed 15 amperes at 125 volts or 10 
amperes at 250 volts if individual overload protection is omitted.

         Table K-4--Receptacle Ratings for Various Size Circuits
------------------------------------------------------------------------
           Circuit rating amperes             Receptacle rating amperes
------------------------------------------------------------------------
15.........................................  Not over 15.
20.........................................  15 or 20.
30.........................................  30.
40.........................................  40 or 50.
50.........................................  50.
------------------------------------------------------------------------

    (c) Outside conductors and lamps--(1) 600 volts, nominal, or less. 
Paragraphs (c)(1)(i) through (c)(1)(iv) of this section apply to branch 
circuit, feeder, and service conductors rated 600 volts, nominal, or 
less and run outdoors as open conductors.
    (i) Conductors on poles. Conductors supported on poles shall provide 
a horizontal climbing space not less than the following:
    (A) Power conductors below communication conductors--30 inches (762 
mm) .
    (B) Power conductors alone or above communication conductors: 300 
volts or less--24 inches (610 mm); more than 300 volts--30 inches (762 
mm).
    (C) Communication conductors below power conductors: with power 
conductors 300 volts or less--24 inches (610 mm); more than 300 volts--
30 inches (762 mm).
    (ii) Clearance from ground. Open conductors shall conform to the 
following minimum clearances:
    (A) 10 feet (3.05 m)--above finished grade, sidewalks, or from any 
platform or projection from which they might be reached.
    (B) 12 feet (3.66 m)--over areas subject to vehicular traffic other 
than truck traffic.
    (C) 15 feet (4.57 m)--over areas other than those specified in 
paragraph (c)(1)(ii)(D) of this section that are subject to truck 
traffic.
    (D) 18 feet (5.49 m)--over public streets, alleys, roads, and 
driveways.
    (iii) Clearance from building openings. Conductors shall have a 
clearance of at least 3 feet (914 mm) from windows, doors, fire escapes, 
or similar locations. Conductors run above the top level of a window are 
considered to be out of reach from that window and, therefore, do not 
have to be 3 feet (914 mm) away.
    (iv) Clearance over roofs. Conductors above roof space accessible to 
employees on foot shall have a clearance from the highest point of the 
roof surface of not less than 8 feet (2.44 m) vertical clearance for 
insulated conductors, not less than 10 feet (3.05 m) vertical or 
diagonal clearance for covered conductors, and not less than 15 feet 
(4.57 m) for bare conductors, except that:
    (A) Where the roof space is also accessible to vehicular traffic, 
the vertical clearance shall not be less than 18 feet (5.49 m), or
    (B) Where the roof space is not normally accessible to employees on 
foot, fully insulated conductors shall have a vertical or diagonal 
clearance of not less than 3 feet (914 mm), or
    (C) Where the voltage between conductors is 300 volts or less and 
the roof has a slope of not less than 4 inches (102 mm) in 12 inches 
(305 mm), the clearance from roofs shall be at least 3 feet (914 mm), or
    (D) Where the voltage between conductors is 300 volts or less and 
the conductors do not pass over more than 4 feet (1.22 m) of the 
overhang portion of the roof and they are terminated at a through-the-
roof raceway or support, the clearance from roofs shall be at least 18 
inches (457 mm).
    (2) Location of outdoor lamps. Lamps for outdoor lighting shall be 
located below all live conductors, transformers, or other electric 
equipment,

[[Page 250]]

unless such equipment is controlled by a disconnecting means that can be 
locked in the open position or unless adequate clearances or other 
safeguards are provided for relamping operations.
    (d) Services--(1) Disconnecting means--(i) General. Means shall be 
provided to disconnect all conductors in a building or other structure 
from the service-entrance conductors. The disconnecting means shall 
plainly indicate whether it is in the open or closed position and shall 
be installed at a readily accessible location nearest the point of 
entrance of the service-entrance conductors.
    (ii) Simultaneous opening of poles. Each service disconnecting means 
shall simultaneously disconnect all ungrounded conductors.
    (2) Services over 600 volts, nominal. The following additional 
requirements apply to services over 600 volts, nominal.
    (i) Guarding. Service-entrance conductors installed as open wires 
shall be guarded to make them accessible only to qualified persons.
    (ii) Warning signs. Signs warning of high voltage shall be posted 
where unauthorized employees might come in contact with live parts.
    (e) Overcurrent protection--(1) 600 volts, nominal, or less. The 
following requirements apply to overcurrent protection of circuits rated 
600 volts, nominal, or less.
    (i) Protection of conductors and equipment. Conductors and equipment 
shall be protected from overcurrent in accordance with their ability to 
safely conduct current. Conductors shall have sufficient ampacity to 
carry the load.
    (ii) Grounded conductors. Except for motor-running overload 
protection, overcurrent devices shall not interrupt the continuity of 
the grounded conductor unless all conductors of the circuit are opened 
simultaneously.
    (iii) Disconnection of fuses and thermal cutouts. Except for devices 
provided for current-limiting on the supply side of the service 
disconnecting means, all cartridge fuses which are accessible to other 
than qualified persons and all fuses and thermal cutouts on circuits 
over 150 volts to ground shall be provided with disconnecting means. 
This disconnecting means shall be installed so that the fuse or thermal 
cutout can be disconnected from its supply without disrupting service to 
equipment and circuits unrelated to those protected by the overcurrent 
device.
    (iv) Location in or on premises. Overcurrent devices shall be 
readily accessible. Overcurrent devices shall not be located where they 
could create an employee safety hazard by being exposed to physical 
damage or located in the vicinity of easily ignitible material.
    (v) Arcing or suddenly moving parts. Fuses and circuit breakers 
shall be so located or shielded that employees will not be burned or 
otherwise injured by their operation.
    (vi) Circuit breakers--(A) Circuit breakers shall clearly indicate 
whether they are in the open (off) or closed (on) position.
    (B) Where circuit breaker handles on switchboards are operated 
vertically rather than horizontally or rotationally, the up position of 
the handle shall be the closed (on) position.
    (C) If used as switches in 120-volt, fluorescent lighting circuits, 
circuit breakers shall be marked ``SWD.''
    (2) Over 600 volts, nominal. Feeders and branch circuits over 600 
volts, nominal, shall have short-circuit protection.
    (f) Grounding. Paragraphs (f)(1) through (f)(11) of this section 
contain grounding requirements for systems, circuits, and equipment.
    (1) Systems to be grounded. The following systems which supply 
premises wiring shall be grounded:
    (i) Three-wire DC systems. All 3-wire DC systems shall have their 
neutral conductor grounded.
    (ii) Two-wire DC systems. Two-wire DC systems operating at over 50 
volts through 300 volts between conductors shall be grounded unless they 
are rectifier-derived from an AC system complying with paragraphs 
(f)(1)(iii), (f)(1)(iv), and (f)(1)(v) of this section.
    (iii) AC circuits, less than 50 volts. AC circuits of less than 50 
volts shall be grounded if they are installed as overhead conductors 
outside of buildings or if they are supplied by transformers and the 
transformer primary supply system is ungrounded or exceeds 150 volts to 
ground.

[[Page 251]]

    (iv) AC systems, 50 volts to 1000 volts. AC systems of 50 volts to 
1000 volts shall be grounded under any of the following conditions, 
unless exempted by paragraph (f)(1)(v) of this section:
    (A) If the system can be so grounded that the maximum voltage to 
ground on the ungrounded conductors does not exceed 150 volts;
    (B) If the system is nominally rated 480Y/277 volt, 3-phase, 4-wire 
in which the neutral is used as a circuit conductor;
    (C) If the system is nominally rated 240/120 volt, 3-phase, 4-wire 
in which the midpoint of one phase is used as a circuit conductor; or
    (D) If a service conductor is uninsulated.
    (v) Exceptions. AC systems of 50 volts to 1000 volts are not 
required to be grounded if the system is separately derived and is 
supplied by a transformer that has a primary voltage rating less than 
1000 volts, provided all of the following conditions are met:
    (A) The system is used exclusively for control circuits,
    (B) The conditions of maintenance and supervision assure that only 
qualified persons will service the installation,
    (C) Continuity of control power is required, and
    (D) Ground detectors are installed on the control system.
    (2) Separately derived systems. Where paragraph (f)(1) of this 
section requires grounding of wiring systems whose power is derived from 
generator, transformer, or converter windings and has no direct 
electrical connection, including a solidly connected grounded circuit 
conductor, to supply conductors originating in another system, paragraph 
(f)(5) of this section shall also apply.
    (3) Portable and vehicle-mounted generators--(i) Portable 
generators. Under the following conditions, the frame of a portable 
generator need not be grounded and may serve as the grounding electrode 
for a system supplied by the generator:
    (A) The generator supplies only equipment mounted on the generator 
and/or cord- and plug-connected equipment through receptacles mounted on 
the generator, and
    (B) The noncurrent-carrying metal parts of equipment and the 
equipment grounding conductor terminals of the receptacles are bonded to 
the generator frame.
    (ii) Vehicle-mounted generators. Under the following conditions the 
frame of a vehicle may serve as the grounding electrode for a system 
supplied by a generator located on the vehicle:
    (A) The frame of the generator is bonded to the vehicle frame, and
    (B) The generator supplies only equipment located on the vehicle 
and/or cord- and plug-connected equipment through receptacles mounted on 
the vehicle or on the generator, and
    (C) The noncurrent-carrying metal parts of equipment and the 
equipment grounding conductor terminals of the receptacles are bonded to 
the generator frame, and
    (D) The system complies with all other provisions of this section.
    (iii) Neutral conductor bonding. A neutral conductor shall be bonded 
to the generator frame if the generator is a component of a separately 
derived system. No other conductor need be bonded to the generator 
frame.
    (4) Conductors to be grounded. For AC premises wiring systems the 
identified conductor shall be grounded.
    (5) Grounding connections--(i) Grounded system. For a grounded 
system, a grounding electrode conductor shall be used to connect both 
the equipment grounding conductor and the grounded circuit conductor to 
the grounding electrode. Both the equipment grounding conductor and the 
grounding electrode conductor shall be connected to the grounded circuit 
conductor on the supply side of the service disconnecting means, or on 
the supply side of the system disconnecting means or overcurrent devices 
if the system is separately derived.
    (ii) Ungrounded systems. For an ungrounded service-supplied system, 
the equipment grounding conductor shall be connected to the grounding 
electrode conductor at the service equipment. For an ungrounded 
separately derived system, the equipment

[[Page 252]]

grounding conductor shall be connected to the grounding electrode 
conductor at, or ahead of, the system disconnecting means or overcurrent 
devices.
    (6) Grounding path. The path to ground from circuits, equipment, and 
enclosures shall be permanent and continuous.
    (7) Supports, enclosures, and equipment to be grounded--(i) Supports 
and enclosures for conductors. Metal cable trays, metal raceways, and 
metal enclosures for conductors shall be grounded, except that:
    (A) Metal enclosures such as sleeves that are used to protect cable 
assemblies from physical damage need not be grounded; and
    (B) Metal enclosures for conductors added to existing installations 
of open wire, knob-and-tube wiring, and nonmetallic-sheathed cable need 
not be grounded if all of the following conditions are met:
    (1) Runs are less than 25 feet (7.62 m);
    (2) Enclosures are free from probable contact with ground, grounded 
metal, metal laths, or other conductive materials; and
    (3) Enclosures are guarded against employee contact.
    (ii) Service equipment enclosures. Metal enclosures for service 
equipment shall be grounded.
    (iii) Fixed equipment. Exposed noncurrent-carrying metal parts of 
fixed equipment which may become energized shall be grounded under any 
of the following conditions:
    (A) If within 8 feet (2.44 m) vertically or 5 feet (1.52 m) 
horizontally of ground or grounded metal objects and subject to employee 
contact.
    (B) If located in a wet or damp location and subject to employee 
contact.
    (C) If in electrical contact with metal.
    (D) If in a hazardous (classified) location.
    (E) If supplied by a metal-clad, metal-sheathed, or grounded metal 
raceway wiring method.
    (F) If equipment operates with any terminal at over 150 volts to 
ground; however, the following need not be grounded:
    (1) Enclosures for switches or circuit breakers used for other than 
service equipment and accessible to qualified persons only;
    (2) Metal frames of electrically heated appliances which are 
permanently and effectively insulated from ground; and
    (3) The cases of distribution apparatus such as transformers and 
capacitors mounted on wooden poles at a height exceeding 8 feet (2.44 m) 
above ground or grade level.
    (iv) Equipment connected by cord and plug. Under any of the 
conditions described in paragraphs (f)(7)(iv)(A) through (f)(7)(iv)(C) 
of this section, exposed noncurrent-carrying metal parts of cord- and 
plug-connected equipment which may become energized shall be grounded:
    (A) If in a hazardous (classified) location (see Sec. 1926.407).
    (B) If operated at over 150 volts to ground, except for guarded 
motors and metal frames of electrically heated appliances if the 
appliance frames are permanently and effectively insulated from ground.
    (C) If the equipment is one of the types listed in paragraphs 
(f)(7)(iv)(C)(1) through (f)(7)(iv)(C)(5) of this section. However, even 
though the equipment may be one of these types, it need not be grounded 
if it is exempted by paragraph (f)(7)(iv)(C)(6).
    (1) Hand held motor-operated tools;
    (2) Cord- and plug-connected equipment used in damp or wet locations 
or by employees standing on the ground or on metal floors or working 
inside of metal tanks or boilers;
    (3) Portable and mobile X-ray and associated equipment;
    (4) Tools likely to be used in wet and/or conductive locations; and
    (5) Portable hand lamps.
    (6) Tools likely to be used in wet and/or conductive locations need 
not be grounded if supplied through an isolating transformer with an 
ungrounded secondary of not over 50 volts. Listed or labeled portable 
tools and appliances protected by a system of double insulation, or its 
equivalent, need not be grounded. If such a system is employed, the 
equipment shall be distinctively marked to indicate that the tool or 
appliance utilizes a system of double insulation.

[[Page 253]]

    (v) Nonelectrical equipment. The metal parts of the following 
nonelectrical equipment shall be grounded: Frames and tracks of 
electrically operated cranes; frames of nonelectrically driven elevator 
cars to which electric conductors are attached; hand-operated metal 
shifting ropes or cables of electric elevators, and metal partitions, 
grill work, and similar metal enclosures around equipment of over IkV 
between conductors.
    (8) Methods of grounding equipment--(i) With circuit conductors. 
Noncurrent-carrying metal parts of fixed equipment, if required to be 
grounded by this subpart, shall be grounded by an equipment grounding 
conductor which is contained within the same raceway, cable, or cord, or 
runs with or encloses the circuit conductors. For DC circuits only, the 
equipment grounding conductor may be run separately from the circuit 
conductors.
    (ii) Grounding conductor. A conductor used for grounding fixed or 
movable equipment shall have capacity to conduct safely any fault 
current which may be imposed on it.
    (iii) Equipment considered effectively grounded. Electric equipment 
is considered to be effectively grounded if it is secured to, and in 
electrical contact with, a metal rack or structure that is provided for 
its support and the metal rack or structure is grounded by the method 
specified for the noncurrent-carrying metal parts of fixed equipment in 
paragraph (f)(8)(i) of this section. Metal car frames supported by metal 
hoisting cables attached to or running over metal sheaves or drums of 
grounded elevator machines are also considered to be effectively 
grounded.
    (9) Bonding. If bonding conductors are used to assure electrical 
continuity, they shall have the capacity to conduct any fault current 
which may be imposed.
    (10) Made electrodes. If made electrodes are used, they shall be 
free from nonconductive coatings, such as paint or enamel; and, if 
practicable, they shall be embedded below permanent moisture level. A 
single electrode consisting of a rod, pipe or plate which has a 
resistance to ground greater than 25 ohms shall be augmented by one 
additional electrode installed no closer than 6 feet (1.83 m) to the 
first electrode.
    (11) Grounding of systems and circuits of 1000 volts and over (high 
voltage)--(i) General. If high voltage systems are grounded, they shall 
comply with all applicable provisions of paragraphs (f)(1) through 
(f)(10) of this section as supplemented and modified by this paragraph 
(f)(11).
    (ii) Grounding of systems supplying portable or mobile equipment. 
Systems supplying portable or mobile high voltage equipment, other than 
substations installed on a temporary basis, shall comply with the 
following:
    (A) Portable and mobile high voltage equipment shall be supplied 
from a system having its neutral grounded through an impedance. If a 
delta-connected high voltage system is used to supply the equipment, a 
system neutral shall be derived.
    (B) Exposed noncurrent-carrying metal parts of portable and mobile 
equipment shall be connected by an equipment grounding conductor to the 
point at which the system neutral impedance is grounded.
    (C) Ground-fault detection and relaying shall be provided to 
automatically de-energize any high voltage system component which has 
developed a ground fault. The continuity of the equipment grounding 
conductor shall be continuously monitored so as to de-energize 
automatically the high voltage feeder to the portable equipment upon 
loss of continuity of the equipment grounding conductor.
    (D) The grounding electrode to which the portable or mobile 
equipment system neutral impedance is connected shall be isolated from 
and separated in the ground by at least 20 feet (6.1 m) from any other 
system or equipment grounding electrode, and there shall be no direct 
connection between the grounding electrodes, such as buried pipe, fence 
or like objects.
    (iii) Grounding of equipment. All noncurrent-carrying metal parts of 
portable equipment and fixed equipment including their associated 
fences, housings, enclosures, and supporting structures shall be 
grounded. However, equipment which is guarded by location and isolated 
from ground need not

[[Page 254]]

be grounded. Additionally, pole-mounted distribution apparatus at a 
height exceeding 8 feet (2.44 m) above ground or grade level need not be 
grounded.

[51 FR 25318, July 11, 1986, as amended at 54 FR 24334, June 7, 1989; 61 
FR 5510, Feb. 13, 1996]





Previous  Home  Next