[Code of Federal Regulations]
[Title 29, Volume 8]
[Revised as of July 1, 2007]
From the U.S. Government Printing Office via GPO Access
[CITE: 29CFR1926.404]
[Page 247-254]
TITLE 29--LABOR
CHAPTER XVII--OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT
OF LABOR
PART 1926_SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION--Table of Contents
Subpart K_Electrical
Sec. 1926.404 Wiring design and protection.
(a) Use and identification of grounded and grounding conductors--(1)
Identification of conductors. A conductor used as a grounded conductor
shall be identifiable and distinguishable from all other conductors. A
conductor used as an equipment grounding conductor shall be identifiable
and distinguishable from all other conductors.
(2) Polarity of connections. No grounded conductor shall be attached
to any terminal or lead so as to reverse designated polarity.
[[Page 248]]
(3) Use of grounding terminals and devices. A grounding terminal or
grounding-type device on a receptacle, cord connector, or attachment
plug shall not be used for purposes other than grounding.
(b) Branch circuits--(1) Ground-fault protection--(i) General. The
employer shall use either ground fault circuit interrupters as specified
in paragraph (b)(1)(ii) of this section or an assured equipment
grounding conductor program as specified in paragraph (b)(1)(iii) of
this section to protect employees on construction sites. These
requirements are in addition to any other requirements for equipment
grounding conductors.
(ii) Ground-fault circuit interrupters. All 120-volt, single-phase,
15- and 20-ampere receptacle outlets on construction sites, which are
not a part of the permanent wiring of the building or structure and
which are in use by employees, shall have approved ground-fault circuit
interrupters for personnel protection. Receptacles on a two-wire,
single-phase portable or vehicle-mounted generator rated not more than
5kW, where the circuit conductors of the generator are insulated from
the generator frame and all other grounded surfaces, need not be
protected with ground-fault circuit interrupters.
(iii) Assured equipment grounding conductor program. The employer
shall establish and implement an assured equipment grounding conductor
program on construction sites covering all cord sets, receptacles which
are not a part of the building or structure, and equipment connected by
cord and plug which are available for use or used by employees. This
program shall comply with the following minimum requirements:
(A) A written description of the program, including the specific
procedures adopted by the employer, shall be available at the jobsite
for inspection and copying by the Assistant Secretary and any affected
employee.
(B) The employer shall designate one or more competent persons (as
defined in Sec. 1926.32(f)) to implement the program.
(C) Each cord set, attachment cap, plug and receptacle of cord sets,
and any equipment connected by cord and plug, except cord sets and
receptacles which are fixed and not exposed to damage, shall be visually
inspected before each day's use for external defects, such as deformed
or missing pins or insulation damage, and for indications of possible
internal damage. Equipment found damaged or defective shall not be used
until repaired.
(D) The following tests shall be performed on all cord sets,
receptacles which are not a part of the permanent wiring of the building
or structure, and cord- and plug-connected equipment required to be
grounded:
(1) All equipment grounding conductors shall be tested for
continuity and shall be electrically continuous.
(2) Each receptacle and attachment cap or plug shall be tested for
correct attachment of the equipment grounding conductor. The equipment
grounding conductor shall be connected to its proper terminal.
(E) All required tests shall be performed:
(1) Before first use;
(2) Before equipment is returned to service following any repairs;
(3) Before equipment is used after any incident which can be
reasonably suspected to have caused damage (for example, when a cord set
is run over); and
(4) At intervals not to exceed 3 months, except that cord sets and
receptacles which are fixed and not exposed to damage shall be tested at
intervals not exceeding 6 months.
(F) The employer shall not make available or permit the use by
employees of any equipment which has not met the requirements of this
paragraph (b)(1)(iii) of this section.
(G) Tests performed as required in this paragraph shall be recorded.
This test record shall identify each receptacle, cord set, and cord- and
plug-connected equipment that passed the test and shall indicate the
last date it was tested or the interval for which it was tested. This
record shall be kept by means of logs, color coding, or other effective
means and shall be maintained until replaced by a more current record.
The record shall be made available on the jobsite for inspection by the
Assistant Secretary and any affected employee.
[[Page 249]]
(2) Outlet devices. Outlet devices shall have an ampere rating not
less than the load to be served and shall comply with the following:
(i) Single receptacles. A single receptacle installed on an
individual branch circuit shall have an ampere rating of not less than
that of the branch circuit.
(ii) Two or more receptacles. Where connected to a branch circuit
supplying two or more receptacles or outlets, receptacle ratings shall
conform to the values listed in Table K-4.
(iii) Receptacles used for the connection of motors. The rating of
an attachment plug or receptacle used for cord- and plug-connection of a
motor to a branch circuit shall not exceed 15 amperes at 125 volts or 10
amperes at 250 volts if individual overload protection is omitted.
Table K-4--Receptacle Ratings for Various Size Circuits
------------------------------------------------------------------------
Circuit rating amperes Receptacle rating amperes
------------------------------------------------------------------------
15......................................... Not over 15.
20......................................... 15 or 20.
30......................................... 30.
40......................................... 40 or 50.
50......................................... 50.
------------------------------------------------------------------------
(c) Outside conductors and lamps--(1) 600 volts, nominal, or less.
Paragraphs (c)(1)(i) through (c)(1)(iv) of this section apply to branch
circuit, feeder, and service conductors rated 600 volts, nominal, or
less and run outdoors as open conductors.
(i) Conductors on poles. Conductors supported on poles shall provide
a horizontal climbing space not less than the following:
(A) Power conductors below communication conductors--30 inches (762
mm) .
(B) Power conductors alone or above communication conductors: 300
volts or less--24 inches (610 mm); more than 300 volts--30 inches (762
mm).
(C) Communication conductors below power conductors: with power
conductors 300 volts or less--24 inches (610 mm); more than 300 volts--
30 inches (762 mm).
(ii) Clearance from ground. Open conductors shall conform to the
following minimum clearances:
(A) 10 feet (3.05 m)--above finished grade, sidewalks, or from any
platform or projection from which they might be reached.
(B) 12 feet (3.66 m)--over areas subject to vehicular traffic other
than truck traffic.
(C) 15 feet (4.57 m)--over areas other than those specified in
paragraph (c)(1)(ii)(D) of this section that are subject to truck
traffic.
(D) 18 feet (5.49 m)--over public streets, alleys, roads, and
driveways.
(iii) Clearance from building openings. Conductors shall have a
clearance of at least 3 feet (914 mm) from windows, doors, fire escapes,
or similar locations. Conductors run above the top level of a window are
considered to be out of reach from that window and, therefore, do not
have to be 3 feet (914 mm) away.
(iv) Clearance over roofs. Conductors above roof space accessible to
employees on foot shall have a clearance from the highest point of the
roof surface of not less than 8 feet (2.44 m) vertical clearance for
insulated conductors, not less than 10 feet (3.05 m) vertical or
diagonal clearance for covered conductors, and not less than 15 feet
(4.57 m) for bare conductors, except that:
(A) Where the roof space is also accessible to vehicular traffic,
the vertical clearance shall not be less than 18 feet (5.49 m), or
(B) Where the roof space is not normally accessible to employees on
foot, fully insulated conductors shall have a vertical or diagonal
clearance of not less than 3 feet (914 mm), or
(C) Where the voltage between conductors is 300 volts or less and
the roof has a slope of not less than 4 inches (102 mm) in 12 inches
(305 mm), the clearance from roofs shall be at least 3 feet (914 mm), or
(D) Where the voltage between conductors is 300 volts or less and
the conductors do not pass over more than 4 feet (1.22 m) of the
overhang portion of the roof and they are terminated at a through-the-
roof raceway or support, the clearance from roofs shall be at least 18
inches (457 mm).
(2) Location of outdoor lamps. Lamps for outdoor lighting shall be
located below all live conductors, transformers, or other electric
equipment,
[[Page 250]]
unless such equipment is controlled by a disconnecting means that can be
locked in the open position or unless adequate clearances or other
safeguards are provided for relamping operations.
(d) Services--(1) Disconnecting means--(i) General. Means shall be
provided to disconnect all conductors in a building or other structure
from the service-entrance conductors. The disconnecting means shall
plainly indicate whether it is in the open or closed position and shall
be installed at a readily accessible location nearest the point of
entrance of the service-entrance conductors.
(ii) Simultaneous opening of poles. Each service disconnecting means
shall simultaneously disconnect all ungrounded conductors.
(2) Services over 600 volts, nominal. The following additional
requirements apply to services over 600 volts, nominal.
(i) Guarding. Service-entrance conductors installed as open wires
shall be guarded to make them accessible only to qualified persons.
(ii) Warning signs. Signs warning of high voltage shall be posted
where unauthorized employees might come in contact with live parts.
(e) Overcurrent protection--(1) 600 volts, nominal, or less. The
following requirements apply to overcurrent protection of circuits rated
600 volts, nominal, or less.
(i) Protection of conductors and equipment. Conductors and equipment
shall be protected from overcurrent in accordance with their ability to
safely conduct current. Conductors shall have sufficient ampacity to
carry the load.
(ii) Grounded conductors. Except for motor-running overload
protection, overcurrent devices shall not interrupt the continuity of
the grounded conductor unless all conductors of the circuit are opened
simultaneously.
(iii) Disconnection of fuses and thermal cutouts. Except for devices
provided for current-limiting on the supply side of the service
disconnecting means, all cartridge fuses which are accessible to other
than qualified persons and all fuses and thermal cutouts on circuits
over 150 volts to ground shall be provided with disconnecting means.
This disconnecting means shall be installed so that the fuse or thermal
cutout can be disconnected from its supply without disrupting service to
equipment and circuits unrelated to those protected by the overcurrent
device.
(iv) Location in or on premises. Overcurrent devices shall be
readily accessible. Overcurrent devices shall not be located where they
could create an employee safety hazard by being exposed to physical
damage or located in the vicinity of easily ignitible material.
(v) Arcing or suddenly moving parts. Fuses and circuit breakers
shall be so located or shielded that employees will not be burned or
otherwise injured by their operation.
(vi) Circuit breakers--(A) Circuit breakers shall clearly indicate
whether they are in the open (off) or closed (on) position.
(B) Where circuit breaker handles on switchboards are operated
vertically rather than horizontally or rotationally, the up position of
the handle shall be the closed (on) position.
(C) If used as switches in 120-volt, fluorescent lighting circuits,
circuit breakers shall be marked ``SWD.''
(2) Over 600 volts, nominal. Feeders and branch circuits over 600
volts, nominal, shall have short-circuit protection.
(f) Grounding. Paragraphs (f)(1) through (f)(11) of this section
contain grounding requirements for systems, circuits, and equipment.
(1) Systems to be grounded. The following systems which supply
premises wiring shall be grounded:
(i) Three-wire DC systems. All 3-wire DC systems shall have their
neutral conductor grounded.
(ii) Two-wire DC systems. Two-wire DC systems operating at over 50
volts through 300 volts between conductors shall be grounded unless they
are rectifier-derived from an AC system complying with paragraphs
(f)(1)(iii), (f)(1)(iv), and (f)(1)(v) of this section.
(iii) AC circuits, less than 50 volts. AC circuits of less than 50
volts shall be grounded if they are installed as overhead conductors
outside of buildings or if they are supplied by transformers and the
transformer primary supply system is ungrounded or exceeds 150 volts to
ground.
[[Page 251]]
(iv) AC systems, 50 volts to 1000 volts. AC systems of 50 volts to
1000 volts shall be grounded under any of the following conditions,
unless exempted by paragraph (f)(1)(v) of this section:
(A) If the system can be so grounded that the maximum voltage to
ground on the ungrounded conductors does not exceed 150 volts;
(B) If the system is nominally rated 480Y/277 volt, 3-phase, 4-wire
in which the neutral is used as a circuit conductor;
(C) If the system is nominally rated 240/120 volt, 3-phase, 4-wire
in which the midpoint of one phase is used as a circuit conductor; or
(D) If a service conductor is uninsulated.
(v) Exceptions. AC systems of 50 volts to 1000 volts are not
required to be grounded if the system is separately derived and is
supplied by a transformer that has a primary voltage rating less than
1000 volts, provided all of the following conditions are met:
(A) The system is used exclusively for control circuits,
(B) The conditions of maintenance and supervision assure that only
qualified persons will service the installation,
(C) Continuity of control power is required, and
(D) Ground detectors are installed on the control system.
(2) Separately derived systems. Where paragraph (f)(1) of this
section requires grounding of wiring systems whose power is derived from
generator, transformer, or converter windings and has no direct
electrical connection, including a solidly connected grounded circuit
conductor, to supply conductors originating in another system, paragraph
(f)(5) of this section shall also apply.
(3) Portable and vehicle-mounted generators--(i) Portable
generators. Under the following conditions, the frame of a portable
generator need not be grounded and may serve as the grounding electrode
for a system supplied by the generator:
(A) The generator supplies only equipment mounted on the generator
and/or cord- and plug-connected equipment through receptacles mounted on
the generator, and
(B) The noncurrent-carrying metal parts of equipment and the
equipment grounding conductor terminals of the receptacles are bonded to
the generator frame.
(ii) Vehicle-mounted generators. Under the following conditions the
frame of a vehicle may serve as the grounding electrode for a system
supplied by a generator located on the vehicle:
(A) The frame of the generator is bonded to the vehicle frame, and
(B) The generator supplies only equipment located on the vehicle
and/or cord- and plug-connected equipment through receptacles mounted on
the vehicle or on the generator, and
(C) The noncurrent-carrying metal parts of equipment and the
equipment grounding conductor terminals of the receptacles are bonded to
the generator frame, and
(D) The system complies with all other provisions of this section.
(iii) Neutral conductor bonding. A neutral conductor shall be bonded
to the generator frame if the generator is a component of a separately
derived system. No other conductor need be bonded to the generator
frame.
(4) Conductors to be grounded. For AC premises wiring systems the
identified conductor shall be grounded.
(5) Grounding connections--(i) Grounded system. For a grounded
system, a grounding electrode conductor shall be used to connect both
the equipment grounding conductor and the grounded circuit conductor to
the grounding electrode. Both the equipment grounding conductor and the
grounding electrode conductor shall be connected to the grounded circuit
conductor on the supply side of the service disconnecting means, or on
the supply side of the system disconnecting means or overcurrent devices
if the system is separately derived.
(ii) Ungrounded systems. For an ungrounded service-supplied system,
the equipment grounding conductor shall be connected to the grounding
electrode conductor at the service equipment. For an ungrounded
separately derived system, the equipment
[[Page 252]]
grounding conductor shall be connected to the grounding electrode
conductor at, or ahead of, the system disconnecting means or overcurrent
devices.
(6) Grounding path. The path to ground from circuits, equipment, and
enclosures shall be permanent and continuous.
(7) Supports, enclosures, and equipment to be grounded--(i) Supports
and enclosures for conductors. Metal cable trays, metal raceways, and
metal enclosures for conductors shall be grounded, except that:
(A) Metal enclosures such as sleeves that are used to protect cable
assemblies from physical damage need not be grounded; and
(B) Metal enclosures for conductors added to existing installations
of open wire, knob-and-tube wiring, and nonmetallic-sheathed cable need
not be grounded if all of the following conditions are met:
(1) Runs are less than 25 feet (7.62 m);
(2) Enclosures are free from probable contact with ground, grounded
metal, metal laths, or other conductive materials; and
(3) Enclosures are guarded against employee contact.
(ii) Service equipment enclosures. Metal enclosures for service
equipment shall be grounded.
(iii) Fixed equipment. Exposed noncurrent-carrying metal parts of
fixed equipment which may become energized shall be grounded under any
of the following conditions:
(A) If within 8 feet (2.44 m) vertically or 5 feet (1.52 m)
horizontally of ground or grounded metal objects and subject to employee
contact.
(B) If located in a wet or damp location and subject to employee
contact.
(C) If in electrical contact with metal.
(D) If in a hazardous (classified) location.
(E) If supplied by a metal-clad, metal-sheathed, or grounded metal
raceway wiring method.
(F) If equipment operates with any terminal at over 150 volts to
ground; however, the following need not be grounded:
(1) Enclosures for switches or circuit breakers used for other than
service equipment and accessible to qualified persons only;
(2) Metal frames of electrically heated appliances which are
permanently and effectively insulated from ground; and
(3) The cases of distribution apparatus such as transformers and
capacitors mounted on wooden poles at a height exceeding 8 feet (2.44 m)
above ground or grade level.
(iv) Equipment connected by cord and plug. Under any of the
conditions described in paragraphs (f)(7)(iv)(A) through (f)(7)(iv)(C)
of this section, exposed noncurrent-carrying metal parts of cord- and
plug-connected equipment which may become energized shall be grounded:
(A) If in a hazardous (classified) location (see Sec. 1926.407).
(B) If operated at over 150 volts to ground, except for guarded
motors and metal frames of electrically heated appliances if the
appliance frames are permanently and effectively insulated from ground.
(C) If the equipment is one of the types listed in paragraphs
(f)(7)(iv)(C)(1) through (f)(7)(iv)(C)(5) of this section. However, even
though the equipment may be one of these types, it need not be grounded
if it is exempted by paragraph (f)(7)(iv)(C)(6).
(1) Hand held motor-operated tools;
(2) Cord- and plug-connected equipment used in damp or wet locations
or by employees standing on the ground or on metal floors or working
inside of metal tanks or boilers;
(3) Portable and mobile X-ray and associated equipment;
(4) Tools likely to be used in wet and/or conductive locations; and
(5) Portable hand lamps.
(6) Tools likely to be used in wet and/or conductive locations need
not be grounded if supplied through an isolating transformer with an
ungrounded secondary of not over 50 volts. Listed or labeled portable
tools and appliances protected by a system of double insulation, or its
equivalent, need not be grounded. If such a system is employed, the
equipment shall be distinctively marked to indicate that the tool or
appliance utilizes a system of double insulation.
[[Page 253]]
(v) Nonelectrical equipment. The metal parts of the following
nonelectrical equipment shall be grounded: Frames and tracks of
electrically operated cranes; frames of nonelectrically driven elevator
cars to which electric conductors are attached; hand-operated metal
shifting ropes or cables of electric elevators, and metal partitions,
grill work, and similar metal enclosures around equipment of over IkV
between conductors.
(8) Methods of grounding equipment--(i) With circuit conductors.
Noncurrent-carrying metal parts of fixed equipment, if required to be
grounded by this subpart, shall be grounded by an equipment grounding
conductor which is contained within the same raceway, cable, or cord, or
runs with or encloses the circuit conductors. For DC circuits only, the
equipment grounding conductor may be run separately from the circuit
conductors.
(ii) Grounding conductor. A conductor used for grounding fixed or
movable equipment shall have capacity to conduct safely any fault
current which may be imposed on it.
(iii) Equipment considered effectively grounded. Electric equipment
is considered to be effectively grounded if it is secured to, and in
electrical contact with, a metal rack or structure that is provided for
its support and the metal rack or structure is grounded by the method
specified for the noncurrent-carrying metal parts of fixed equipment in
paragraph (f)(8)(i) of this section. Metal car frames supported by metal
hoisting cables attached to or running over metal sheaves or drums of
grounded elevator machines are also considered to be effectively
grounded.
(9) Bonding. If bonding conductors are used to assure electrical
continuity, they shall have the capacity to conduct any fault current
which may be imposed.
(10) Made electrodes. If made electrodes are used, they shall be
free from nonconductive coatings, such as paint or enamel; and, if
practicable, they shall be embedded below permanent moisture level. A
single electrode consisting of a rod, pipe or plate which has a
resistance to ground greater than 25 ohms shall be augmented by one
additional electrode installed no closer than 6 feet (1.83 m) to the
first electrode.
(11) Grounding of systems and circuits of 1000 volts and over (high
voltage)--(i) General. If high voltage systems are grounded, they shall
comply with all applicable provisions of paragraphs (f)(1) through
(f)(10) of this section as supplemented and modified by this paragraph
(f)(11).
(ii) Grounding of systems supplying portable or mobile equipment.
Systems supplying portable or mobile high voltage equipment, other than
substations installed on a temporary basis, shall comply with the
following:
(A) Portable and mobile high voltage equipment shall be supplied
from a system having its neutral grounded through an impedance. If a
delta-connected high voltage system is used to supply the equipment, a
system neutral shall be derived.
(B) Exposed noncurrent-carrying metal parts of portable and mobile
equipment shall be connected by an equipment grounding conductor to the
point at which the system neutral impedance is grounded.
(C) Ground-fault detection and relaying shall be provided to
automatically de-energize any high voltage system component which has
developed a ground fault. The continuity of the equipment grounding
conductor shall be continuously monitored so as to de-energize
automatically the high voltage feeder to the portable equipment upon
loss of continuity of the equipment grounding conductor.
(D) The grounding electrode to which the portable or mobile
equipment system neutral impedance is connected shall be isolated from
and separated in the ground by at least 20 feet (6.1 m) from any other
system or equipment grounding electrode, and there shall be no direct
connection between the grounding electrodes, such as buried pipe, fence
or like objects.
(iii) Grounding of equipment. All noncurrent-carrying metal parts of
portable equipment and fixed equipment including their associated
fences, housings, enclosures, and supporting structures shall be
grounded. However, equipment which is guarded by location and isolated
from ground need not
[[Page 254]]
be grounded. Additionally, pole-mounted distribution apparatus at a
height exceeding 8 feet (2.44 m) above ground or grade level need not be
grounded.
[51 FR 25318, July 11, 1986, as amended at 54 FR 24334, June 7, 1989; 61
FR 5510, Feb. 13, 1996]